Skip to content
Contact details to be supplied
  • 17 Years of Manufacturing
  • Custom Connector Solutions
  • Precision Design
Magtor
Magtor

Main navigation

Contact details to be supplied
Industry Insights & Technical Updates

Magnetic Connector Wiring: Power, Signal Mapping and Validation

Published on August 18, 2026
Black ribbed cable seal with two mounting holes and visible stripped wire ends.

In a magnetic electrical interface, spring contacts carry power and signals while magnets assist mating and retention. Begin wiring with an agreed map of power, return and signal functions on both halves. Check continuity, shorts and polarity with power disconnected before progressing to supply-voltage and operating tests.

Contact count is not a wiring standard. Four-, five- and six-contact assemblies can have different power, ground, data, detection or control assignments according to the device circuit. Confirm the actual mapping rather than copying one from a similar-looking part.

What the contacts and magnets do

The interface separates mechanical guidance from electrical transfer:

magnetic contact assembly
  • Magnets assist alignment and retain the matching halves.

  • Conductive contacts connect the assigned power or signal paths.

Four-wire magnetic connector assembly with a black, green, white and red harness.

Magnetic attachment normally does not assign electrical functions. Define each contact as the required supply, return, data, detection or other circuit path in the device design.

One possible allocation is shown below:

PinIllustrative assignmentCircuit role
Pin 1V+Positive supply path
Pin 2GNDPower return or ground reference as designed
Pin 3Signal / DataAssigned data path
Pin 4Signal / DataSecond assigned data path
Pin 5ID / DetectIdentification or mating detection
Pin 6ControlCharging or device-control function

Scroll horizontally to view every column.

This table is an example, not a standard pinout. Use the approved drawing and electrical assignment for the exact mating assembly.

For charging with digital data, the complete electrical implementation must meet the intended protocol. USB-IF publishes specifications covering USB interfaces; assigning signal contacts alone does not demonstrate compliance with those requirements.

USB-IF USB 2.0 specification reference

Defining power, return and signal functions

Before terminating wires, document the mapping of both mating halves, including their viewing directions and contact numbering.

Original six-contact magnetic connector pin assignment and power, ground and data functions.

Identify these four function groups:

Positive supply — V+

This path supplies the device. Select the voltage and allowable current for the product, then verify the connector and conductor limits for that load.

Power return or reference — GND

The return completes the supply circuit. It may also provide a signal reference, depending on the circuit; do not assume every isolated or differential interface uses it in the same way.

Signal paths

Other contacts may serve communication, sensors, audio, detection, charging control or auxiliary functions where the device electronics support them.

Detection and reserved contacts

Additional paths can identify the device, detect engagement, enable charging or remain reserved for a defined future function.

A conceptual four-contact allocation for power with USB 2.0-style data is:

PinIllustrative function
Pin 1V+
Pin 2GND
Pin 3D+
Pin 4D−

Scroll horizontally to view every column.

D+ and D− identify USB data functions, not arbitrary interchangeable lines. An intended USB design needs the applicable electrical implementation and validation. USB-IF publishes the relevant specifications and compliance requirements; this example is not certification or standard USB physical pin numbering.

Approve the contact mapping before PCB layout and cable production. Recording the mating views and polarity helps avoid reversed supply connections, mismatched cable assemblies and orientation errors.

Example allocations for different contact counts

Contact count limits the available paths, but internal connections or parallel contacts can reduce the number of independent circuits. Functions still come from the electrical design.

Two-contact magnetic interface

Two-contact magnetic interface

A simple two-contact example assigns:

Pin 1 → V+; Pin 2 → GND

Such a layout may suit basic DC supply or charging where no separate signal contact is needed. Confirm the actual supply and protection requirements.

Three-contact magnetic interface

Three-contact magnetic interface

One three-contact example assigns:

Pin 1 → V+; Pin 2 → GND; Pin 3 → Signal / Detect

The third path can serve communication, temperature sensing, engagement detection or another low-current function when implemented by the device circuit.

Four-contact magnetic interface

Four-contact magnetic interface

One possible power-and-data example assigns:

Pin 1 → V+; Pin 2 → GND; Pin 3 → Data+; Pin 4 → Data−

This allocation can combine power and signals only where the contact design and electronics suit the required protocol. The example does not establish a universal four-contact wiring rule.

Five- or six-contact magnetic interface

five-contactsix-contact magnetic interface

Extra contacts allow more function choices. A six-contact example is:

Pin 1 → V+; Pin 2 → GND; Pin 3 → Data+; Pin 4 → Data−; Pin 5 → ID / Detect; Pin 6 → Control / Auxiliary Signal

Confirm this example against the actual drawing; it is not a standard six-contact magnetic pinout.

Choosing a magnetic contact count; functions depend on the device circuit.

Choose the mapping from:

  • Device supply voltage and current

  • Required signal protocol

  • PCB routing and layout

  • Cable conductor and construction requirements

  • Each contact’s allowable current

  • Signal-integrity requirements

  • Permitted mating orientation

  • Applicable safety requirements

Higher-current designs may parallel contacts for supply or return. Evaluate current sharing, contact states and temperature rise; the total allowable current cannot simply be multiplied by the number of parallel pins.

Cable termination and PCB integration

Depending on the assembly, integration may use wire soldering, PCB mounting or a combined connector-and-cable construction. Select a termination supported by the actual part.

Four-contact cable soldering and five-contact PCB integration examples with termination and mounting checks.

Soldered wire termination

For a cable-side assembly, follow this sequence:

  1. Confirm the approved contact map.

  2. Identify the conductor assigned to each contact.

  3. Prepare the stripped conductor ends.

  4. Solder each conductor to its designated terminal.

  5. Inspect neighbouring terminals for solder bridges.

  6. Provide the required insulation and strain relief.

  7. Check continuity with power disconnected before energizing.

Poor solder joints can add resistance or fail when the cable moves. IPC J-STD-001 addresses soldered electrical and electronic assemblies and can inform the agreed workmanship requirements. The reference does not establish that this connector or its assembly is certified to the standard.

IPC soldered-assembly requirements

Board-side termination

Depending on the model, board integration may use:

  • SMT mounting

  • Through-hole electrical mounting (THT; sometimes labelled DIP)

  • Solder pads

  • A product-specific PCB footprint

Match the footprint to the approved pitch, contact positions, orientation and installed working height. Verify the complete mating tolerance stack as well as the solder geometry.

For combined power and signals, review load-current paths alongside sensitive routing. The connector forms part of the electrical interface, so mechanical fit alone is not sufficient.

Checks before connecting the device

Keep the new assembly disconnected from operating power until the initial wiring checks are complete.

Four-contact connector with multimeter and checklist for continuity, short circuits, polarity, voltage and load tests.

Begin with unpowered electrical checks.

Verify the complete continuity map

With power disconnected, confirm that every contact reaches its intended counterpart. Use the defined views and numbering for both halves, especially where the mating faces appear mirrored.

For a numbering scheme already defined in the drawing, an example is:

Male Pin 1 → Female Pin 1; Male Pin 2 → Female Pin 2

Check every contact, not only the first two.

Look for unintended connections

With power disconnected, verify that the positive path is not unintentionally joined to ground or neighbouring signals.

Small terminal spacing makes careful bridge inspection especially relevant in compact multi-contact assemblies.

Verify polarity in the permitted mating states

Check that the allowed engagement orientations cannot unintentionally exchange the positive supply and return paths.

Mechanical keying, magnet polarity, housing geometry, PCB design and circuit protection can reduce connection errors. Assess the implemented features rather than assuming magnetic attachment guarantees correct polarity.

Confirm supply voltage before attaching the device

After the unpowered checks, energize the supply side in the planned validation setup and measure the contact voltage.

Attach the target device only after the measured voltage and polarity agree with the design.

Validate at the intended operating load

Passing an unpowered continuity check does not demonstrate acceptable performance at operating current. Evaluate the assembled interface under the intended load.

Prototype checks include:

  • Voltage drop

  • Contact resistance

  • Contact-assembly temperature

  • Stability during charging

  • Stability of the required signals

  • Performance over the specified mating duty

A USB implementation also needs the relevant electrical compliance checks. Basic continuity testing does not establish USB compatibility or certification.

Wiring faults to avoid

Include these fault mechanisms in the integration review.

Copying a pinout from a different assembly

There is no universal assignment shared by all three-, four-, five- or six-contact magnetic parts. A particular series may have its own approved drawing.

Use that actual drawing to verify every function.

Exchanging supply and return

Reversed polarity can damage the connected circuitry. Specify mating orientation and electrical polarity during design, then validate possible engagement states and protection.

Overloading a contact intended for signals

Contact size, spring structure, plating and resistance influence allowable current. Check each path’s rating and installed thermal behaviour; identical-looking contacts need not have identical load assignments.

Overlooking voltage loss

The contact interface, cable conductors and solder joints all add resistance and voltage drop.

Assess that loss particularly carefully for low-voltage charging at higher current.

Planning power and sensitive-signal routing separately

Develop the contact allocation and PCB routing together when the same interface carries power and data.

Where practical, separate high-current paths from sensitive routing to support the required signal performance and electrical validation.

Treating sealing as a connector-only property

For water, sweat, dust or outdoor use, assess the assembled device. The contact part alone cannot establish the finished product’s ingress or chemical-exposure performance.

The housing, seals, cable exit, adhesive, O-rings and assembly process all contribute to protection. IEC 60529 classifies enclosure ingress protection; specify the required test conditions and validate the assembled configuration. An IP classification does not establish every sweat, corrosion or wet-operation requirement.

IEC ingress-protection classification reference

Developing a product-specific pinout

Start with the device’s electrical functions and constraints, then determine the required contacts.

Six wiring risks involving four-contact connectors: assignment, polarity, current, soldering, strain relief and routing.

Define the following inputs before selecting or customizing the assembly:

Supply voltage → Current → Power-contact count → Signal-contact count → Signal type → PCB space → Cable exit → Mating orientation → Environmental requirements

Two contacts may suffice for a simple charger. Four, five or six contacts can provide more allocation options where charging, communication and detection are needed together, subject to the actual circuit and connector design.

Magtor can review contact assignments, working height, retention, housing, plating, orientation and cable construction for a custom project. Evaluate these inputs against the existing PCB and enclosure; matching that envelope remains a design and validation task rather than a guarantee of zero device changes.

Wiring review summary

Define the supply, return and signal functions on both halves first. Terminate the cable or board to that map, complete the unpowered continuity, short and polarity checks, then confirm supply voltage before attaching the device. Validate the representative assembly under operating conditions as well.

Contact count and visible position cannot substitute for an approved electrical map. Build the assignment from the application’s functions and requirements, including the mating views, current paths and signals.

Frequently asked questions

How should the wire size be selected?

Select conductor size from the required current, cable length and allowable voltage drop, within the connector and cable limits. Higher-current paths generally need larger conductors than low-current signals. Confirm the complete conductor and contact specifications before approving the wiring.

Can one magnetic interface carry power and data?

It can, where suitable contacts are allocated to supply, return and signals and the complete design supports the required interface. Validate current capacity, signal type, pin assignment and PCB routing together.

Can the contact functions be tailored?

A custom assignment can combine power, ground, data, identification, charging control or auxiliary signals. Agree the mapping and mating views before PCB layout and cable assembly production; customization does not establish support for every protocol.

When is reverse-polarity protection needed?

Where a permitted or foreseeable incorrect mating state could reverse supply and return, assess suitable reverse-polarity protection. Keying, magnet polarity, housing geometry and electronic protection can reduce damage risks, but verify the combined design rather than relying on one feature alone.

What should be checked when data is unstable?

Inspect solder quality, contact resistance, pin mapping, cable length, power interference and signal routing. Check grounding, contact condition and the intended protocol requirements before deciding whether the connector structure needs to change.

Discuss your project

17 years of manufacturing, precision design and prototyping. Contact details pending. Development test — no email will be sent.

Magtor

Work with Magtor for precision connector design, prototyping and production at scale, supported by 17 years of manufacturing experience.

Three people at a connector exhibition booth with neutral signage.
  • 17 Years of Manufacturing

    Manufacturing experience helps guide your connector project from development into production.

  • Prototyping and Mold Making

    Prototype development and mold making in-house to suit your connector design.

  • Technical Support and Solution Development

    Engineering support to review specifications and develop a suitable connection solution.

Technical enquiries & global support

Contact details to be supplied

Manufacturing headquarters

406, Building 3, No. 12, Zhenyuan Road, Wusha, Chang'an Town, Dongguan City, Guangdong Province, China

Custom Magnetic Connection Solutions

Service goal: review project specifications and respond within 24 hours. This development preview does not send inquiries or schedule replies.

Development test: submissions are checked on this preview only. No email is sent. Development test — no email will be sent.

Your project information is treated as confidential and used to review your requirements.